Interpretation of the fault code of international air conditioners

Air conditioner type Error code Code interpretation
Daikin A1 Malfunction of indoor unit PCB Malfunction due to noise Defect of indoor unit PCB.
Malfunction of the printed circuit board of the indoor unit due to a noise defect in the printed circuit board of the indoor unit.
A3 Malfunction of drain level control system Drain piping clogging, improper drain piping work Defect of drain pump. Defect of float switch.
Malfunction in the drain level control system. Clogged drain pipes, incorrect operation of the drain pipes. Defect in the drain pump. Defective float switch.
A4 Malfunction of freezing protection Shortage of water volume Low water temperature setting Defect of 26WL. Defect of water temperature thermistor.
Freeze protection malfunction Low water volume Low water temperature setting Defective 26WL. Defective water temperature thermistor.
A5 High pressure control in heating, freeze-up protection control in cooling Clogged air filter of indoor unit and short-circuit Defect of indoor unit heat exchanger thermistor.
High pressure control in heating, freeze protection control in cooling. Clogged air filter of indoor unit and short circuit Defect of heat exchanger thermistor of indoor unit.
A6 Fan motor locked, overload, overcurrent Defect of connector contact Defect of indoor unit PCB Defect of fan motor.
Fan motor blocked, overload, overcurrent Defective connector contact Defective printed circuit board of the indoor unit Defective fan motor.
A7 Malfunction of swing flap motor Failure of swing flap motor, Defect of indoor unit PCB Jammed swing mechanism/blade.
Swing flap motor failure Swing flap motor failure, defect in the internal unit PCB swing mechanism/blade.
A8 Malfunction of power supply Overcurrent of AC input, Defect of power supply voltage.
AC input overcurrent fault, power supply voltage fault.
A9 Malfunction of electronic expansion valve drive Defect of electronic expansion valve coil, Defect of indoor unit PCB, Defect of connector contact.
Malfunction of the electronic expansion valve motor Defective coil of the electronic expansion valve, defect in the printed circuit board of the indoor unit, defect in the connector connection.
AA Heater overheat 26WH is activated.
The 26WH overheater is activated.
AF Malfunction of a humidifier system Water leakage of humidifier (option), Failure of swing float switch. Improper drain piping incline.
Humidifier system malfunction Water leaking from humidifier (optional), rocker float switch failure. Improper slope of drainage pipes
A.H Malfunction of dust collector of air cleaner Defect of dust collecting element Defect of high voltage power supply unit Stained insulator part Defect of indoor unit PCB.
Defect in the air cleaner dust collector Defect in the dust collection element Defect in the high voltage power supply unit Stained insulating part Defect in the indoor unit PCB.
AJ Malfunction of capacity setting (Indoor unit PCB) Capacity setting adapter is not installed when replacing PCB Defect of indoor unit PCB.
Capacitance setting fault (indoor unit printed circuit board) The capacitance setting adapter is not installed when replacing the printed circuit board defect in the indoor unit printed circuit board.
C1 Failure of transmission (between indoor unit PCB and fan PCB) Defect of transmission of fan motor control driver. 
Transmission failure (between indoor unit PCB and fan PCB) Defect in fan motor control driver transmission.
C4 Malfunction of liquid pipe thermistor for heat exchanger Defect of connector contact. Defect of liquid pipe thermistor for heat exchanger.
Malfunction of the thermistor of the liquid tube of the heat exchanger Defect in the connector connection. Defective fluid pipe of the heat exchanger.
C5 Malfunction of gas pipe thermistor for heat exchanger Defect of connector contact. Defect of gas pipe thermistor for heat exchanger.
Malfunction of the thermistor of the gas tube of the heat exchanger Defect in the connector connection. Defective gas tube thermistor of the heat exchanger.
C6 Malfunction of fan motor control driver Defect of fan motor sensor system Defect of fan motor control driver.
Fan motor control driver defective Fan motor sensor system defective Fan motor control driver defective.
C7 Front panel driving motor fault Defect of front panel driving motor Defect of limit switch.
Front panel drive malfunction Front panel drive motor defective Limit switch defective.
C9 Malfunction of air suction thermistor Defect of connector contact Defect of thermistor for air suction.
Defect in the thermistor of the suction air Defect in the contact of the connector Defect in the thermistor of the suction air.
CA Malfunction of discharge air thermistor Defect of connector contact. Defect of thermistor for air discharge.
Air discharge thermistor malfunction Defect in connector connection. Defective air discharge thermistor.
CC Malfunction of humidity sensor system Defect of connector contact Defect of humidity sensor.
Defect in the humidity sensing system Defect in the connector contact Defect in the humidity sensor.
Midea E0 EEPROM parameter error
EEPROM parameter error
E1 Indoor / outdoor units communication protection
Protect indoor/outdoor unit connections
E2 Zero-crossing signal error
Zero crossing signal error
E3 Fan speed out of control
Fan speed is out of control
E5 Open or short circuit of outdoor temperature sensor
Open or short circuit of the external temperature sensor
E6 Open or short circuit of room or evaporator temperature sensor
Opening or short circuit of the room or evaporator temperature sensor
P0 IGBT over-strong current protection
Over-current protection in IGBT
P1 Over voltage or too under voltage protection
Over voltage or under voltage protection
P2 Temperature protection of compressor top.
Temperature protection of the upper part of the compressor.
P4 Inverter compressor drive error
Inverter compressor motor fault
YORK E0 Indoor EEPROM (Electrically Erasable Programmable Read-Only Memory) error
Internal Error EEPROM (Electrically Erasable Programmable Read Only Memory)
E1 Indoor and outdoor unit communication malfunction
Malfunction in the connection of the internal and external unit
E3 Indoor fan speed malfunction
Internal fan speed malfunction
E4 Indoor room temperature sensor error
Error in internal room temperature sensor
E5 Evaporator coil temperature sensor error
Evaporator coil temperature sensor error
EC Refrigerant leak detection system malfunction
Malfunction in the refrigerant gas leak detection system
EE Water level alarm malfunction
Water level alarm malfunction
E8 Dual indoor unit (twin model only) communication malfunction
Duplex indoor unit (dual model only) Communication failure
E9 Other twin model malfunction
Malfunction of the other twin model
E0 Overload protection
Overload protection
F1 Outdoor temperature sensor error
Error in external temperature sensor
F2 Outdoor condenser pipe sensor error
Outdoor condenser tube sensor error
F3 Discharge air temperature sensor error
Air temperature sensor error discharge
F4 Outdoor EEPROM (Electrically Erasable Programmable Read-Only Memory) error
Error in external EEPROM (electrically erasable programmable read-only memory)
F5 Outdoor fan speed (DC fan motor only) malfunction
Outdoor fan speed malfunction (DC fan motor only)
F6 T2b sensor error
T2b sensor error
F7 Auto-lifting panel communication error
Automatic lifting plate connection error
F8 Auto-lifting panel malfunction
Automatic lifting plate malfunction
F9 Auto-lifting panel is open
The automatic lifting panel is open
P0 Inverter module IPM protection
IPM protection for inverter module
P1 High/Low voltage protection
High/low voltage protection
P2 Compressor top overheating protection
Higher compressor overheating protection
P3 Outdoor low temperature protection
Outdoor low temperature protection
P4 Compressor drive error
Compressor motor fault
P5 Mode conflict
Conflict situation
P6 Compressor low-pressure protection
Low pressure protection for compressor
P7 Outdoor IGBT sensor error
Outdoor IGBT sensor error
AUX E1 Plastic temp sensor is abnormal. 
The plastic temperature sensor is abnormal.
E2 Copper temp sensor is abnormal (outdoor)
Abnormal copper temperature sensor (external)
E3 Copper temp sensor is abnormal (indoor)
Abnormal copper temperature sensor (internal)
E4 PG motor feedback is abnormal
Abnormal PG motor reactions
E5 Abnormality of outdoor unit
Defect in the external unit
E6 Over-current oprotection
Over-current protection
E7 External feedback failure
Failure of external feedback
E8 Overheat protection
Overheat protection
E9 Water pump failure
Water pump failure
dF Indicates "dF"or defrosting indicator displays
Indicates that the “dF” or defrost indicator appears
L1 Failure of coiled pipe sensor
Coiled tube sensor failure
L2 Failure of room temperature sensor
Room temperature sensor failure
L6 Without feedback of internal fan motor
No internal fan motor feedback
BEKO H1 Means defrosting status. It's the normal phenomenon.
Means defrosting condition. It is a natural phenomenon.
E5 It can be eliminated after restarting the unit. If not, please contact qualified professionals for service.
It can be removed after restarting the unit. If not, please contact qualified professionals for service.
U8 It can be eliminated after restarting the unit. If not, please contact qualified professionals for service.
It can be removed after restarting the unit. If not, please contact qualified professionals for service.
H6 It can be eliminated after restarting the unit. If not, please contact qualified professionals for service.
It can be removed after restarting the unit. If not, please contact qualified professionals for service.
C5 Please contact qualified professionals for service.
Please contact qualified professionals for service.
F1 Please contact qualified professionals for service.
Please contact qualified professionals for service.
F2 Please contact qualified professionals for service.
Please contact qualified professionals for service.
Carrier E0 Indoor unit EEPROM parameter error
EEPROM indoor unit parameter error
E1 Indoor/outdoor units communication error
Error in connection of indoor/outdoor units
E3 Indoor fan speed has been out of control
The indoor fan speed is out of control
E4 Indoor room temperature sensor T1 open circuit or short circuit
Indoor room temperature sensor T1 open circuit or short circuit
E5 Evaporator coil temperature sensor T2 open circuit or short circuit
Evaporator coil temperature sensor T2 is open circuit or short circuit
EC Refrigerant Leakage Detection
Refrigerant leak detection
F1 Outdoor ambient temperature sensor T4 open circuit or short circuit
Outdoor ambient temperature sensor T4 open circuit or short circuit
F2 Condenser coil temperature sensor T3 open circuit or short circuit
Condenser coil temperature sensor T3 is open circuit or short circuit
F3 Compressor discharge temperature sensor T5 open circuit or short circuit
Compressor discharge temperature sensor T5 open circuit or short circuit
F4 Outdoor unit EEPROM parameter error
Outdoor unit parameter error EEPROM
F5 Outdoor fan speed has been out of control
The outdoor fan speed is out of control
P0 IPM malfunction or IGBT over-strong current protection
IPM fault or over-current protection in IGBT
P1 Over voltage or over low voltage protection
Overvoltage or undervoltage protection
P2 High temperature protection of compressor top diagnosis and solution
High temperature protection for diagnostics and compressor top solution
P4 Inverter compressor drive error
Inverter compressor motor fault
P5 Mode conflict
Conflict situation
P6 Compressor voltage protection
Compressor voltage protection
Chigo E1 Condenser temperature aensor fault
Condenser temperature sensor error
E2 Room temp. sensor fault
Room temperature. Sensor error
E3 Coil temp. sensor fault
coil temperature. Sensor error
E4 Outdoor unit abnormal
The outdoor unit is abnormal
E5 No feedback signal of indoor fan
There is no feedback signal for the internal fan
E6 No over zero signal
No signal is more than zero
E7 Outdoor feedback fault
Outdoor feedback error
E8 Frost protection/over heat protection
Frost protection/overheat protection
F1 Communication fault
connection error
F2 Ambient temp. sensor fault
Ambient temperature. Sensor error
F3 Coil pipe temp. sensor of indoor unit fault
Coil pipe temperature. Indoor unit error sensor
F4 Fan motor of indoor
Indoor fan motor
F5 Module of outdoor unit fault
Outdoor unit error module
F6 Ambient temp. sensor of outdoor fault
Ambient temperature. Outdoor fault sensor
F7 Coil pipe temp. sensor of outdoor unit fault
Coil pipe temperature. Outdoor unit error sensor
F8 Suction temp. sensor of compressor fault
Suction temperature. Compressor fault sensor
F9 Discharge temp. sensor of compressor fault
Discharge temperature. Compressor fault sensor
F.A Inductor of current or voltage fault
Inductor current or voltage error
FC Compressor drive fault
Compressor motor fault
FD Phase lacking or phase sequence fault
Phase missing or error in phase sequence
FE Gas return sensor fault
Gas return sensor error
FF Other fault
Another mistake
P1 Temp. of evaporator protection
Temperature. To protect the evaporator
P2 Overheat, over current protection of inverter module
High temperature, over current protection for inverter module
P3 Over current protection
Over current protection
P4 Discharge temp. of compressor protection
Discharge temperature. From compressor protection
P5 Over heat of compressor top protection
Overheating of compressor overhead protection
P6 Suction temp. of compressor protection
Suction temperature. From compressor protection
P7 Low or high voltage protection
Low or high voltage protection
P8 Low presser of gas return protection
Low presser to protect gas return
P9 High pressure of discharge protection
High pressure discharge protection
PA High temp. of condenser protection
high temperature. From condenser protection
PC High temp. of outdoor ambient protection
high temperature. Protect the external environment
PF Other protection
Other protection
DF Defrost indication
Defrost indicator
Delonghi LE Low Temperature (frost prevention). The appliance is fitted with a frost protection device to avoid excessive formation of ice. The appliance starts up again automatically when the defrosting process is completed.
Low temperature (frost prevention). The device is equipped with a frost protection device to avoid excessive ice formation. The machine starts working again automatically when the defrosting process is complete.
H.L High Level (internal tray full). Empty the internal safety tray following the instructions in the section “End of season operations”. If it reoccurs in cooling mode, contact your local authorized customer services. In heating mode: empty the internal tray.
High level (inner drawer is full). Empty the internal safety drawer following the instructions in the “End of Season Operations” section. If it reoccurs in cooling mode, contact your local authorized customer services. In heating mode: Empty the inner tray.
CF Change filter. When this message is displayed, the water filter needs replacing as described in the section: “Replacing the limescale filter”.
Change filter. When this message is displayed, the water filter must be replaced as described in the section: “Replacing the Limescale Filter”.
PF Probe Failure (sensor damaged). If this is displayed, contact your local authorized service centre.
Probe failure (sensor damage). If this is displayed, contact your local authorized service centre.
F1 Failure 1. This message could appear if the water filter is particularly clogged. See section: “Replacing the limescale filter”. If the filter has been replaced recently, contact your local authorized service centre.
Failure 1. This message may appear if the water filter is particularly clogged. See section: “Replacing the limescale filter”. If the filter has recently been replaced, contact your local authorized service center.
Lo Low Temperature - Room temperature is too low.
Low temperature - The room temperature is too low.
H1 High Temperature - Room temperature is too high.
High temperature - The room temperature is too high.
E1 Probe Failure (Sensor Damaged).
Probe failure (sensor damaged).
Fujitsu E0:00 Coms error - indoor to remote
Error comes - internal to remote
E1:00 Coms error - indoor to outdoor
Error comes - internal to external
E2:00 Return air thermistor open circuit
Air return thermistor open circuit
E3:00 Return air thermistor short circuit
Return short circuit thermistor
E4:00 Indoor coil thermistor open
The internal coil thermistor is open
E5:00 Indoor coil thermistor shorted
Internal thermistor shortened coil
E6:00 Outdoor coil thermistor open
Open the thermistor outdoors
E7:00 Outdoor coil thermistor shorted
Shortened outdoor thermistor coil
EA:00 Outdoor ambient thermistor open
Open the outer circumference thermistor
Eb:00 Outdoor ambient thermistor shorted
Shorted the thermistor to the external surroundings
Ec:00 Discharge pipe theistor open
The resistive discharge tube is open
Ed:00 Discharge pipe thermistor shorted
Drain tube thermistor shorted
EE:00 High pressure problem
High pressure problem
EF:00 Discharge pipe temp. Problem - too high = short of gas
Discharge pipe temperature. Problem - too high = lack of gas
O.O ID to RC Comms Fail
Identifier for RC communications failed
O1 ID to OD Comms Fail
ID to OD Comms Fail
O2 ID Air Sensor Open
Open the ID air sensor
O3 ID Air Sensor Close
Air sensor ID is close
O4 ID Pipe Sensor Open
The sensor tube ID is open
O5 ID Pipe Sensor Close
Close sensor tube ID
O6 OD Pipe Sensor Failure
OD tube sensor failure
O8 Power Source Connection Failure
Power supply connection failure
O9 Drain Problem Float switch operated
Drain problem float switch has been triggered
OA OD Air Sensor Failure
OD air sensor failure
O.C Discharge sensor failure
Vacuum sensor failure
OE Outdoor High Pressure Heatsink error
Error in outdoor high-pressure refrigeration chamber
11 OD PCB Failure
OD PCB failure
12 ID Fan Fail
Fan ID failed
13 OD Signal Abnormal ID signal error
Error signal ID signal OD abnormal
14 OD EEPROM Failure
OD EEPROM failed
15 Compressor Temp Failure
Compressor temperature failure
16 Pressure Switch Error
Pressure switch error
17 IPM Error
IPM error
18 CT Error
CT error
19 Active Filter Module Error
Error in the active filter unit
1A Compressor Failure
Compressor failure
1B OD Fan Failure
OD fan failure
1C Inverter to PCB Comms Fail
Inverter to PCB Comms failed
1D 2 Way Valve sensor Failure
2 way LED sensor failure
1E Expansion Valve Error
Expansion valve error
1F Connection ID Unit Error
Error in connection ID module
20 Indoor manual switch abnormal
Internal manual switch is abnormal
24 Excessive high pressure protection on cooling
Protection against excessively high cooling pressure
25 PFC circuit error
PFC circuit fault
26 Indoor signal error
Internal signal error
27 Indoor signal error
Internal signal error
28 Indoor heat exchanger temperature error
Internal heat exchanger temperature error
29 Outdoor heat exchanger temperature (middle) error
External heat exchanger temperature error (middle)
2A Power supply frequency detection error
Error detecting power supply frequency
2B Compressor temperature error
Compressor temperature error
2C Four-way valve abnormal
Four-way valve abnormal
General 01 Indoor unit does not accept signal from outdoor unit
The indoor unit does not accept a signal from the outdoor unit
02 Room temperature sensor open
The room temperature sensor is open
03 Room temperature sensor short-circuited
Room temperature sensor short circuited
04 Indoor heat exchanger temperature sensor open
The internal heat exchanger temperature sensor is open
05 Indoor heat exchanger temperature sensor short circuited
Internal heat exchanger temperature sensor short circuit
06 Outdoor heat exchanger temperature sensor
Outdoor heat exchanger temperature sensor
08 Power source connection error
Error connecting the power supply
09 Float switch operated
Float switch works
0A Outdoor temperature sensor error
Error in external temperature sensor
0c Discharge pipe temperature sensor
Discharge pipe temperature sensor
11 Model abnormal/Indoor EPROM Abnormal
Abnormal model/internal EPROM abnormal
12 Indoor fan abnormal
Abnormal internal fan
13 Outdoor unit does not accept the signal from indoor unit
The outdoor unit does not accept the signal from the indoor unit
14 Excessive outdoor pressure (permanent stop)
Excessive external pressure (permanent stop)
15 Compressor temperature sensor
Compressor temperature sensor
16 Pressure switch error
Pressure switch error
17 IPM error
IPM error
18 CT error
CT error
19 Active filter module (AFM) error
Active Filter Module (AFM) fault
1A Compressor does not operate
The compressor is not working
1b Outdoor unit fan error
Outdoor unit fan error
1c Communication error (inverter to multi controller)
Communication error (inverter to multi controller)
1d 2 way valve sensor error
2 way sensor fault sensor
1E Expansion valve error
Expansion valve error
1F Connection indoor unit error
Error connecting indoor unit
GE E0 On 70 Pint models only - when water is not pumped out while the unit is running under the Pump mode, E0 and the pump light will flash on the display.
E1 Electronic control board function error. Unplug the window air conditioner for 1 minute and then plug it back in to reset the electronic control board. If the code doesn't clear, unplug the window air conditioner and check the wire harness connections on the electronic control board. Check the electronic control board for visible damage such as a burn mark. Replace the electronic control board if it's damaged or defective.
E4 Water bucket is full or defective bucket float switch. If the collection bucket is full, empty the bucket. If the bucket is not full, unplug the air conditioner and check the wire harness connections on the electronic control board. Check for a pinched or damaged wire in the wire harness between the electronic control board and the collection bucket float switch. Check the float switch for damage. If the float switch is defective, replace it.
88 When power is connected to the unit, “88” will be displayed, this is normal. If a fault or error code appears on the display of the dehumidifier, disconnect power to the unit for 30 seconds. If the fault code reappears, review the Troubleshooting Tips in your Owner's Manual.
Gree E1 Refrigerant system high pressure protection
E2 Anti-freezing protection
E4 Compressor exhaust high temperature protection
E5 AC over-current protection
E6 Communication failure between indoor unit and outdoor unit
E8 Anti-high temperature protection
H6 No feedback of indoor fan motor
C5 Jumper cap malfunction protection
F0 Refrigerant Leakage Protection
F1 Indoor ambient sensor open or short circuit
F2 Indoor tube sensor open or short circuit
F3 Outdoor ambient sensor open or short circuit
F4 Outdoor tube sensor open or short circuit
F5 Exhaust sensor open or short circuit
F6 Over load limit / drop frequency
F8 Over current limit / drop frequency
F9 High exhaust temperature limit / drop frequency
P.H Over voltage protection for PN
U5 AC current detect circuit malfunction
U4 Compressor reverse protection
P5 Over compressor phase current protection
b5 Inlet tube sensor malfunction
L3 Outdoor DC fan motor malfunction
b7 Outlet tube sensor malfunction
FC Door malfunction
FE Compressor overload sensor malfunction
H1 Defrosting
H2 Static clearing dust protection
H3 Compressor over load protection
H4 System abnormal protection
H5 IPM protection
HC PFC protection
H7 Compressor loss step protection
H0 Heating anti-high temperature drop frequency
Lc Startup failed
U2 Compressor protection against loss of phase
U1 Compressor phase current detection circuit malfunction
HE Compressor demagnetization protection
EE Loading EEPROM malfunction
P6 Communication failure between main board and driver board
PU Capacitor charge malfunction
P7 IPM sensor circuit malfunction
P8 IPM high temperature protection
U3 PN voltage drop protection
P.L Low PN voltage protection
PC Current detect circuit malfunction or current sensor malfunction
Ld Compressor loss of phase protection
LE Compressor locked rotary protection
EU IPM over temperature limit / drop frequency
U7 4-way valve reversal abnormal
U8 Disconnection of the exhaust temperature sensor
U9 AC power zero voltage detect error
F.A Over tube temperature drop frequency
FH Anti-freezing limit / drop frequency
oE PFC module temperature protection/PFC module sensor malfunction
Haier  E1 Indoor room temperature sensor failure
E2 Indoor coil temperature sensor failure
E4 EEPROM wrong
E7 Communication failure between indoor and outdoor
E14 Indoor fan motor failure
E18 Temperature cutoff protection
F1 Module failure
F2 Outdoor DC motor failure
F4 Compressor overheat/discharging temperature protection
F5 Module over current / current transducer failure
F6 Outdoor ambient temp. sensor abnormal
F7 Outdoor suction/defrosting temp. sensor abnormal
F8 High pressure abnormal
F9 Low pressure abnormal
F10 No AC power supply
F11 Outdoor PCB EEPROM abnormal
F13 Communication failure between outdoor PCB and module
F14 Compressor discharging temp. sensor failure
F15 Compressor running faulty
F16 Running state-detecting circuit failure
Hisense  00 No trouble
01 Outdoor coil temperature sensor in trouble
02 Compressor temperature sensor in trouble
03 Voltage transformer in trouble
04 Current transformer in trouble
05 IPM module protection
06 Over and under voltage control
07 Communication problem
08 Current overload control
09 Maximum current control
10 Communication trouble (between outdoor unit and driver unit)
11 Outdoor EEPROM in trouble
13 Compressor exhaust temperature too high control
14 Outdoor ambient temperature sensor in trouble
15 Compressor housing temperature control
16 Anti-freeze or overload control
18 DC compressor fails to start
19 DC compressor out of step
33 Room temperature sensor in trouble
34 Indoor coil temperature sensor in trouble
35 Between wire remote controller and indoor unit communication problem
36 Communication between the indoor and outdoor in trouble
37 Water overbrimmed the pump
38 Indoor EEPROM in trouble
39 Indoor fan motor operation abnormal
40 Grid protection alarm (cabinet type)
41 Detecting failures by zero-crossing
F0 Wire remote controller EEPROM failure. Change wire remote controller.
F1 Wire remote controller temperature sensor failure. Change wire remote controller.
F2 Wire remote controller clock IC failure. Change wire remote controller.
F3 Wire remote controller humidity sensor failure. Change wire remote controller.
FE Communication between main control board & Wiring remote controller Fault (display on wiring remote controller).
ER Communication between main control board & display board Fault.
Hitachi P01 Pressure ratio protection control
P02 High pressure increase protection
P03 Inverter current protection
P04 Inverter fin temperature increase protection
P05 Discharge gas temperature increase protection at the upper part of the compressor
P06 Low pressure decrease protection
P09 High pressure decrease protection
P0A Demand current protection control
P0d Low pressure increase protection
P11 Pressure ratio decrease retry
P12 Low pressure increase retry
P13 High pressure increase retry
P14 Constant speed compressor overcurrent retry
P15 Discharge gas temperature increase retry / Low pressure decrease retry
P16 Discharge gas super-heat decrease retry
P17 Inverter anomaly retry
P18 Abnormal Inverter voltage retry / Inverter failure retry
P26 High pressure decrease retry
LG C1 or CH1 Indoor temperature sensor open or closed circuit.
C2 or CH2 Outdoor temperature sensor open or closed circuit.
C4 or CH4 Heat sink temperature sensor open or closed circuit.
C5 or CH5 Communication between indoor and outdoor units.
C6 or CH6 Excessive current at inverter DC power circuit.
C7 or CH7 Excessive compressor current
C8 or CH8 Indoor fan not rotating.
C9 or CH9 Outdoor fan does not rotate.
CA 1. Discharge temp more than130 °C 2. Faulty discharge thermistor
CC EEPROM error
CD Inverter module error
Po System in Power Mode – not a fault
Lo System in test mode – not a fault
Samsung E101 Communication Error (Indoor Outdoor)
E102 Communication Error (Indoor Outdoor)
E121 ROOMTH sensor error
E122 INDOOR MID, INDOOR IN PIPE-TH sensor error
E154 Fan Error (Indoor)
E162 EEPROM Error (Indoor)
E163 Option Error
E203 Time out Comm. (Inv Micom Main Micom)
E221 OUT-TH(Outdoor Temperature) Sensor Error
E231 CON-TH(Cond Temperature) Sensor Error
E251 DIS-TH(Discharge Temperature) Sensor Error
E416 DIS-TH(Discharge Temperature) Over Error
E422 EEV or Valve Close error-Self diagnosis
E440 Prohibit Operation Condition Error (Heating)
E441 Prohibit Operation Condition Error (Cooling)
E458 Fan Error(Outdoor)
E461 Comp Starting Error
E462 AC Input I_Limit Trip Error
E464 IPM Over Current(OC) Error
E465 Comp V_limit/I_limit Error
E466 DC-Link Voltage Under/Over Error
E467 Comp Wire Missing Error
E468 Current Sensor Error
E469 DC-Link Voltage Sensor Error
E470 EEPROM Data Error (no data)
E471 EEPROM Data Error (Main Micom Inv Micom)
E474 Heatsink Sensor Error
E483 Over Voltage Protection Error
E484 PFC Over Load Error
E485 Input Current Sensor Error
E488 AC Input Voltage Sensor Error
E500 Heatsink Over Temperature Error
E554 Gas leak error
Sharp EE Buttons are locked
E0 Water pump malfunction
E1 High pressure protection of compressor
E2 Indoor anti-frozen of compressor
E3 Low pressure protection of compressor
E4 Air discharge high-temperature protection of compressor
E5 Overload protection of compressor
E6 Transmit malfunction
E8 Indoor fan protection
E9 Water flow protection
FF Connected control communications Failure
F0 Malfunction of indoor environment sensor at air return vent
F1 Evaporator sensor malfunction
F2 Condenser sensor malfunction
F3 Outdoor environment sensor malfunction
F4 Malfunction of air discharge sensor
F5 Malfunction of environment sensor on displayer
ee Malfunction of external drive memory chip. Outdoor drive board.
H3 Compressor over load protection. Compressor overload switch.
H4 Overload protection. Evaporator temperature, condenser temperature.
H6 Malfunction of outdoor fan motor. Outdoor fan motor.
U7 Direction changing malfunction of 4-way valve.
P6 Communication malfunction between main control and drive.
EE Malfunction of outdoor main control memory chip. Outdoor main control board.
TCL E0 Indoor/outdoor communication fault
EC Outdoor communication fault
E1 Room temperature sensor (IRT)
E2 Indoor pipe (coil) temperature sensor (IPT)
E3 Outdoor pipe (coil) temperature sensor (OPT)
E4 System abnormal
E5 Model configuration wrong
E6 Indoor fan motor fault
E7 Outdoor temperature sensor
E8 Exhaust temperature sensor
E9 Intelligent power module of drive and module fault
EF Outdoor fan motor fault (DC Motor)
EA Current sensor fault
EE EEPROM fault
EP Temperature switch fault (on top of the compressor)
EU Voltage sensor fault
E.H Intake temperature sensor
P1 Overvoltage / undervoltage protection
P2 Overcurrent protection
P4 Exhaust overtemperature protection
P5 Subcooling protection under cooling mode
P6 Overheating protection under cooling mode
P7 Overheating protection under heating mode
P8 Outdoor overtemperature / undertemperature protection
P9 Drive protection (software control)
P0 Module protection (hardware control)
Toshiba E01 No communication between remote controller and indoor unit.
E02 Local controller failure - unable to transmit
E03 Master indoor unit receives no data to AB
E04 Indoor unit (except twin slave) receives no communications from outdoor unit; can also include klixon on discharge pipe of outdoor unit
E08 Duplicated indoor unit address
E09 2 local controllers connected on a group - both configured as masters
E10 Indoor unit PSB failure
E18 Communications failure between master indoor unit and slave indoor unit or units
F01 Indoor unit TCJ (Liquid) sensor error (Open or Closed circuit - resistance is measured in kΩ
F02 Indoor unit TC2 (Vapour) sesnor error (Open or Closed circuit - resistance is measured in kΩ
F04 Outdoor unit TD (Discharge) senor error (Open or Closed circuit - resistance is measured in kΩ
F06 Outdoor unit TE (Coil) sesnor error (Open or Closed circuit - resistance is emasured in kΩ
F08 Outdoor unit TO (Ambient) sensor error (Open or Closed circuit - resistance is measured in kΩ
F10 Indoor unit TA (Return Air) sesnor error )Open or Closed circuit - resistance is measured in kΩ
F29 Indoor unit PCB failure
H01 Outdoor unit inverter compressor over current detected
H02 Master outdoor unit over current detected shortly after start up
H03 Current detected on Master outdoor unit whilst idle
H06 Outdoor unit Low pressure detected by Ps sensor (0.2 bar -n 2.9 psig)
L03 Indoor unit Duplicated master indoor units in a group
L07 Indoor unit in a group of units previously addressed as a single unit - check addressing
L08 Indoor units addresses not set - check addressing
L09 Indoor units capacity not set (check DN Code 11)
L29 Outdoor unit IPDU error (Number of detected IPDU units is reduced)
L30 Input on indoor PCB CN80 circuit for 1 minute
L31 Outdoor unit PCB error
P01 Indoor unit fan motor error
P03 Outdoor unit High discharge temperature (TD1 exceeded 115°C)
P04 Outdoor unit High pressure switch activated (Detected by high temperature on TE sensor on digital/super digital inverter units)
P07 Outdoor unit PCB heat sink overheated (Temperature over 90°C recorded)
P10 Indoor unit Float switch activated
P12 Indoor unit fan motor error - detected by feedback circuit
P19 Wrong change in temperature recorded (4 way valve error)
P22 Outdoor unit fan motor IPDU error
P26 Outdoor unit Giant transistor short circuit
P29 Outdoor unit Compressor error detected by feedback circuit
P30 Indoor unit Group control follower unit error / duplicated central control addresses
P31 Indoor unit PCB error
C05 Central control Sending error in TCC-Link central control device
C06 Central control Receive error in TCC-Link central control device
C12 Batch alarm for general purpose equipment interface
Westinghouse  E0 Indoor unit EEPROM parameter error.
E1 Indoor/outdoor units communication error.
E2 Zero-crossing signal detection error.
E3 Indoor fan speed has been out of control.
E4 Open circuit or short circuit of indoor room temperature T1 sensor.
E5 Open circuit or short circuit of evaporator coil temperature T2 sensor
EC Refrigerant Leakage Detection
F1 Open circuit or short circuit of outdoor ambient T4 temperature sensor
F2 Open circuit or short circuit of condenser coil temperature T3 sensor
F3 Open circuit or short circuit of compressor discharge T5 temperature sensor
F4 Outdoor unit EEPROM parameter error
P0 IPM malfunction or IGBT over-strong current protection
P1 Over voltage or over low voltage protection
P2 High temperature protection of compressor top diagnosis and solution
P4 Inverter compressor drive error
المقالة السابقة Common air conditioning system malfunctions and how to fix them